Description
Day Tank Re-Circulation/Fuel Conditioner Kit – AC.RKDT
Due to modern engines & critical power situations, better fuel filtration is becoming more important. Generator tanks that often have smaller capacity or day tanks where the fuel also requires re-circulating & conditioning usually require a fuel conditioner kit to be installed.
Features:
- Suitable for use with diesel and heating oil.
- It recirculates & conditions fuel preventing fuel degradation inside the day tank or any tank up to 1,000 litre capacity.
- Ideal for use on generator day tanks when fuel is not used often or when it’s important that the fuel is kept fresh at all times.
- The fuel passes through a pre-filter conditioner, to prevent microbial growth incorporating a 100 micron particle filter & water drain tap makes draining excess water easy.
- Fuel is automatically circulated to ensure the tank content is recirculated 1.5 times every 28 days.
- 230V pump. Power consumption 110Ma. Pump dB rating 68.
- Alarms: the red LED on the front panel indicates either excess water (water sensor) or a blocked filter (low flow sensor). Both will stop the pump. A 230V output then activates when either status is triggered (can be connected to a remote warning device).
- When red LED is lit, check water filter & drain off any water. When this red LED blinks check the particle filter. Then start the pump until fuel reaches the pump, the equipment is ready to operate in automatic mode.
- Timer operates 4 hours continuously 7 days a week (starts when you press the start button on the front panel).
Information:
- If sited outside a weatherproof cover must be fitted.
- Dimensions 310mm H x 240mm W x 130mm D.
- Inlet/Outlet ¼” F BSP. Water drain outlet 1/8” F BSP.
- Important: Must be installed above the maximum level of the tank.