Bolton Town Hall Emergency Fuel Infrastructure: Deploying a Custom 600L StoraFUEL System
Partnering with J W Hinchliffe (Tanks) Ltd to Secure Civic Backup Power
Atlantis Tanks recently collaborated with specialist contractor J W Hinchliffe (Tanks) Ltd to deliver a compact, high-integrity fuel storage solution for Bolton Town Hall. 
Specifically, we engineered and supplied a custom 600 Litre Steel Bunded Diesel/Oil Tank from our StoraFUEL range, designed to function as a dependable daily generator feed unit for municipal emergency power.
Civic infrastructure and local government buildings require continuous, fail-safe power resilience to maintain essential public services during power outages. To meet the space constraints and technical demands of Bolton Town Hall, Atlantis Tanks manufactured a tailored, high-performance steel day tank with dedicated pump mounting provisions, multi-port socket configurations, and complete secondary containment.
Engineering Specifications: 600L StoraFUEL System
The unit was custom-engineered to fit compact site footprints while meeting strict UK environmental mandates and manufacturing standards.
-
Capacity Metrics: 643 Litres Nominal (677L Brimful / 623L Useable with Overfill Prevention Valve)
-
Outer Dimensions: 990mm (L) x 700mm (W) x 1250mm (H) (excluding bearers and fittings)
-
Inner Dimensions: 860mm (L) x 640mm (W) x 1248mm (H)
-
Structural Material: High-grade steel to BS EN 10025-2:2004 standards, featuring internal tank bracing for maximum structural rigidity
-
Secondary Containment: Integrated outer bund providing 110% secondary fluid capacity, fully compliant with Control of Pollution regulations
-
Weight Profile: 171 KG (Dry Weight) / 726 KG (Estimated Wet Weight)
-
High-Performance Coating: ST2 surface preparation with a Zinfos 340WS solvent-borne anti-corrosive primer and self-priming topcoat (150-micron wet / 75-micron dry film thickness in Black)
-
Handling & Support: Full-length structural steel bearers and integrated lifting eyes for safe transport and empty positioning
Technical Socket Architecture and Automation Provisions
Compact day tanks require precise piping integration to regulate fuel transfer between bulk storage units and standby generators. The unit incorporates a custom manifold and controller plate setup:
-
Controller & Pump Provision: Integrated 200mm x 200mm mounting plate designed specifically for a day tank controller unit and pump set
-
Fuel Transfer Sockets: Dedicated 1″ socket for bulk tank fuel supply and 1″ return line socket
-
Suction Line: 1″ top suction point fitted with an internal standpipe
-
Dual Venting System: 2″ tank-to-bund vent and 2″ bund-to-atmosphere vent located at the rear top section
-
Auxiliary Porting: 3x 1.5″ front-top tank sockets, 1x 2″ rear-top tank socket, 1x 1.5″ rear-top bund socket, and 1x 1″ bottom outlet
Turnkey Logistics and Standards Compliance
To streamline installation at the town hall site, Atlantis Tanks coordinated delivery utilizing a specialized HIAB crane offloading facility to place the asset precisely where required. Backed by our standard 10-year tank warranty, this installation underscores our ability to deliver technical fuel storage solutions tailored to public sector and civic infrastructure projects.